Sign In | Join Free | My himfr.com |
|
Ask Lasest Price | |
Brand Name : | KAIXIANG |
Model Number : | AC400-500KW |
Certification : | ISO9001 |
Price : | negotiable |
Payment Terms : | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability : | 20 SETS ONE MONTH |
Delivery Time : | ONE MONTH AFTER GET DEPOSIT |
Variable Resistive Electrical 500Kw Load Bank With Over Heat
Protection
Product Description
1.our load bank an accurately test output power and load capacity with all kinds of generators.
2.System consists of testing/control and load bank, mainly includes AC load bank, data capture system, auto load/unload control system, heat dissipation device, assist control and PC software.
3.User can control load bank through local control panel, also through software
Technical Parameter
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, |
Rated Load Power | Resistive load: 500kW |
Installed Capacity | Resistive load: 500kW |
Load Step | 1,2,2,5,10,10,20,50,100,100,200kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 380VAC/50Hz, 3 phase 4 wire, |
Wire Connection | Load power supply input——Copper bar (star coupling) |
Insulation | F |
Protection Grade | IP21 |
Way of Working | Continuous Working |
Casing Dimensions and Cooling | about 1550*1250*1680mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 750kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤1500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |
Product Advantage
Communication type: through RS232, RS485
Load mode: manual load or automatic load.
Manual load: input power and power factor.
Application
Manufacturers of small gas engines also use load banks to test
newly manufactured engines under various mechanical loads. This is
accomplished by connecting the engine to the load bank via a device
called a dynamometer. Again, engine performance is monitored and,
if necessary, adjustments are made to ensure the product performs
within intended specifications.
![]() |